Invalid Configuration Detected when Launching KEPServerEX V4
Last Update: 12.11.2018
Problem:
When attempting to launch KEPServerEX V4, a message box appears that states "Invalid configuration detected. The server was unable to determine the computer ID. Please run the installation program."
Solution:
Click OK to close the message box, and then do the following:
- Browse to C:\Windows\System32 or C:\Windows\SysWOW64 on 64-bit operating systems.
- Delete the "slf0000.slf" file.
- Launch the Command Prompt using Run As Administrator.
- Change the directory to C:\Program Files\KEPServerEX or C:\Program Files (x86)\KEPServerEX on 64-bit operating systems.
- Next, type "servermain register" and press Enter.
- Next, type "kselogger servermain.exe" and press Enter.
Note: On 64-bit operating systems, a message about "machnm1.exe" may appear. Ignore this message and continue to use KEPServerEX V4.
©