Use the search and browse feature to view Kepware's repository of more than 500 Knowledge Base articles. Narrow your results or type your query into the search field below.

Search Solutions Results By: View All Solutions

Kepware Knowledge Base: Solution


Entering the Local and Remote TSAP for a Siemens S7-200 PLC


Last Update: 11/7/2018

The TSAP is displayed in MicroWin's Ethernet Wizard. When accessed from V memory, the value may be in decimal form. For example, if the TSAP is 10.00, the V memory value will be 1000 hexadecimal or 4096 decimal. The values entered for Local TSAP must be in hexadecimal notation; in this example, the value "1000" would be entered. Users can simply drop the decimal point from the TSAP displayed in the MicroWin Ethernet Wizard.

Note: After the PLC's program is changed, it must be power cycled.