Use the search and browse feature to view Kepware's repository of more than 500 Knowledge Base articles. Narrow your results or type your query into the search field below.

Search Solutions Results By: View All Solutions

Kepware Knowledge Base: Solution


How to Read a Symbolic Variable That Is Local in Scope to an LD Block


Last Update: 11/7/2018

There is an LD block in the Proficy ME project called "BlockName" that has a local symbolic variable called "LocalVariableName". This variable would get added to the Proficy ME Variable List as "BlockName.LocalVariableName". When importing this tag (SNF/CSV import) into KEPServerEX, the tag would be imported as "!BlockName.LocalVariableName" as expected. But when performing a read/write on the tag, the operation would fail. In order to correctly read/write the tag, the tag name must be prefaced with "LDPROG1" and changed to "!LDPROG1.BlockName.LocalVariableName". This is because of a difference in the way Proficy ME saves the variable in the "Variable List" and the "PVT" in the device.

Related Products
GE Ethernet, GE Suite