Unable to Connect to a ThermoWestronics Ethernet Device


Last Update: 11/7/2018

ThermoWestronics Ethernet devices use the Modbus TCP protocol to communicate. This requires a fifth octet to be set that matches the device's Modbus ID. For example, to communicate with a device with an IP address of 192.168.10.100 and a Modbus Device ID of 1, the Device ID set in KEPServerEX should be 192.168.10.100.1.