Using Omron CP1 Series PLCs with Omron FINS Ethernet and Serial Drivers


Last Update: 11/12/2018

When using Kepware's Omron FINS Ethernet and Omron FINS Serial drivers with an Omron CP1 series PLC (CP1E, CP1L, and CP1H ), users should do the following:

  • Select a device model of CJ1.
  • Verify the address ranges for the model in use. The table below displays ranges that were taken from the Omron specifications; however, the best way to see the address ranges for the model in use is with CX Programmer.

Type

Maximum Address

CP1L

CP1H

CP1E

CIO

6143

6143

289

W

511

511

99

H

511

511

49

A

959

959

753

T

4095

4095

255

TS

4095

4095

255

C

4095

4095

255

CS

4095

4095

255

D

( -M ) 32767

( -L ) 0 - 9999 and 32000 -32767

32767

( -E ) 2047

( -N ) 8191

DR

15

15

IR

15

15

TK

31

31

Note: Kepware has not verified driver operation with any of the CP1 series PLCs.