Use the search and browse feature to view Kepware's repository of more than 500 Knowledge Base articles. Narrow your results or type your query into the search field below.

Search Solutions Results By: View All Solutions

Kepware Knowledge Base: Solution


How Are Physical I/O Points Referenced in ROCLINK 800 Software?


Last Update: 11/7/2018

In ROCLINK 800 software, physical I/O points are referenced using a Point Number. For information on how the Point Numbers reconcile with KEPServerEX's Logical Addresses, refer to the table below.

ROCLINK Point NumberKEPServerEX Logical Address
A1-A160-15
B1-B1616-31
C1-C1632-47
D1-D1648-63
E1-E1664-79
......

See Also: Reconciling KEPServerEX Logical Addresses with ROCLINK's Point Numbers

Related Products
Fisher ROC Suite, KEPServerEX