検索機能を使用して 500 を上回る Kepware の知識ベース記事の中から閲覧します。結果を絞り込むか、クエリーを下部の検索フィールドに入力します。

解決策が見つからなかった場合には、当社の PTC eSupport Portal で追加資料を確認することもできます。eSupport Portal へのログインを要求された場合、My Kepware の認証情報を使用できます。My Kepware アカウントが必要ですか? こちらで作成

各種検索方法:
View All Solutions

Kepware Knowledge Base: Solution


NetLink Error Code 0x12 (12) is Posted to the KEPServerEX Event Log


Last Update: 2018/11/12

Possible Cause:
This error code means "Master not into the logical token ring."

Solution:
Verify the following settings to ensure that they are set correctly.

  • In the server, click Device Properties | Communication Parameters. Then, locate the MPI ID setting and verify that it is set to the PLC's MPI address.
  • In the NetLink Configuration Utility (which is located in the server's Utilities sub-directory and can be launched through the Start menu), locate the Own Station Address setting. This is the MPI address of the NetLink itself, and must be set to an address that is not used by the PLC or by any other device on the MPI bus.
  • Set the Highest Station Address of the PLC (or other MPI-bus masters) greater than or equal to the Own Station Address in the NetLink Configuration Utility.