Communicating to Modbus Plus Networks with Hilscher CIF Modbus Plus Cards


Last Update: 2018/11/12

Problem:
Users cannot communicate to devices on a Modbus Plus network when using KEPServerEX's Modbus Plus Driver with a Hilscher CIF Modbus Plus interface card.

Solution:
Ensure that the Hilscher CIF Modbus Plus interface card is assigned a unique Modbus Plus Node Address.

Note:
On Hilscher cards, the default Node Address setting is 16. Because there cannot be duplicate node addresses on the Modbus Plus network, users must ensure that a unique address is set for each node.

Related Products
Modbus Plus, Modbus Suite

Related Protocols
Modbus Plus