使用搜索功能查看 Kepware 的信息库,其中包含 500 多篇知识库文章。缩小搜索结果范围,或在下面的搜索字段中输入您的查询。

或者,如果您无法找到解决方案,我们还有另一个资源:我们的 PTC eSupport Portal。 如果系统提示您登录 eSupport Portal,您可以使用“我的 Kepware”凭据。需要一个“我的 Kepware”帐户吗?在此处创建

搜索解决方案结果:
View All Solutions

Kepware Knowledge Base: Solution


Does KEPServerEX Support Communications with the Netcon 5000 from Woodward?


Last Update: 2018/11/7

Yes, it does. The Modbus Serial driver can be used in Ethernet Encapsulation mode, which is different than using the Modbus Ethernet Driver. For more information, follow the instructions below.

Note: All parameters should be left at their default settings unless an alternate value is stated.

  1. In the Netcon 5000 configuration file, find the function block that determines the port setting. Note this number, since it will be needed in a future step.
  2. Next, add a channel to the server project. In the Device Driver drop-down menu, select Modbus RTU Serial and then click Next.
  3. In Communications, select Use Ethernet encapsulation and then finish defining the channel.
  4. Next, add a device to the channel. In Ethernet Encapsulation, enter the Netcon's IP address and then edit the port number to match the number set earlier in the Netcon 5000 configuration file. Then, choose UDP as the protocol.
  5. In Framing, make sure that the Use Modbus TCP framing checkbox is not checked. Then, finish defining the device.
  6. Users should now be able to communicate with Netcon 5000.

Note: Newer versions of Netcon firmware also support TCP.

Related Products
Modbus Serial, Modbus Suite