Kepware Knowledge Base: Solution


Invalid Configuration Detected when Launching KEPServerEX V4


Last Update: 2018/11/12

Problem:
When attempting to launch KEPServerEX V4, a message box appears that states "Invalid configuration detected. The server was unable to determine the computer ID. Please run the installation program."

Solution:
Click OK to close the message box, and then do the following:

  1. Browse to C:\Windows\System32 or C:\Windows\SysWOW64 on 64-bit operating systems.
  2. Delete the "slf0000.slf" file.
  3. Launch the Command Prompt using Run As Administrator.
  4. Change the directory to C:\Program Files\KEPServerEX or C:\Program Files (x86)\KEPServerEX on 64-bit operating systems.
  5. Next, type "servermain register" and press Enter.
  6. Next, type "kselogger servermain.exe" and press Enter.

    Note: On 64-bit operating systems, a message about "machnm1.exe" may appear. Ignore this message and continue to use KEPServerEX V4.
Related Products
KEPServerEX