使用搜索功能查看 Kepware 的信息库,其中包含 500 多篇知识库文章。缩小搜索结果范围,或在下面的搜索字段中输入您的查询。

或者,如果您无法找到解决方案,我们还有另一个资源:我们的 PTC eSupport Portal。 如果系统提示您登录 eSupport Portal,您可以使用“我的 Kepware”凭据。需要一个“我的 Kepware”帐户吗?在此处创建

搜索解决方案结果:
View All Solutions

Kepware Knowledge Base: Solution


KEPServerEX: What Is the Maximum Number of Client Connections?


Last Update: 2018/11/7

In most cases, the server can support as many client connections as needed; however, the number of process threads for a running application process is limited.

  • Windows XP and older operating systems limit the number of threads per process to 2024.
  • Windows 2003 and higher operating systems limit the number of threads per process based on the resources that are available.

In OPC, each client connection consumes a single thread; each OPC group that is added by an OPC client connection consumes two threads in the server. One additional thread is usually needed per channel for device communications and other purposes. As a result, the maximum number of connections can vary from project to project. In some cases, a project that is moved from an older XP operating system to a new operating system may support fewer connections than expected.

Note: When the thread resource limit is met, attempts to add groups and items will fail with error code 0x8007000E ("E_OutofMemory").