使用搜索功能查看 Kepware 的信息库,其中包含 500 多篇知识库文章。缩小搜索结果范围,或在下面的搜索字段中输入您的查询。

或者,如果您无法找到解决方案,我们还有另一个资源:我们的 PTC eSupport Portal。 如果系统提示您登录 eSupport Portal,您可以使用“我的 Kepware”凭据。需要一个“我的 Kepware”帐户吗?在此处创建

搜索解决方案结果:
View All Solutions

Kepware Knowledge Base: Solution


Unable to Add Item to OPC Server, but LinkMaster Can Connect and Add a Group


Last Update: 2018/11/12

The OPC DA 2.05A specification stipulates that clients (like LinkMaster) are not required to use an access path. Some servers, however, require that clients provide an access path when adding an item. For example, if users do not specify an access path, LinkMaster's Event Viewer may show that it was unable to add an item because the server returned error 0x80070057 ("The parameter is incorrect").

A space character may be all that the server requires in the access path. When using LinkMaster with these types of servers, double-click the link item to open its Link Item Properties. In the Input tab (or Output tab as necessary), enter an access path to meet the requirements of the server.

Related Products
LinkMaster