使用搜索功能查看 Kepware 的信息库,其中包含 500 多篇知识库文章。缩小搜索结果范围,或在下面的搜索字段中输入您的查询。

或者,如果您无法找到解决方案,我们还有另一个资源:我们的 PTC eSupport Portal。 如果系统提示您登录 eSupport Portal,您可以使用“我的 Kepware”凭据。需要一个“我的 Kepware”帐户吗?在此处创建

搜索解决方案结果:
View All Solutions

Kepware Knowledge Base: Solution


Unable to Make Remote OPC DA Connections to the Server


Last Update: 2018/11/7

Problem:
Users are unable to make remote OPC DA connections to the server.

Solution:
KEPServerEX administrators must configure Windows security (including DCOM authentication) for remote OPC DA connections to the server to be successful. For information on configuring Windows to permit remote OPC DA connections, refer to "Remote OPC DA Quick Start Guide".

Note: If the OPC DA client is running as a non-administrative user, KEPServerEX administrators may need to add it to the list of approved users under OPC Enum's Launch and Activation Permissions. For more information, refer to the instructions below.

  1. Log in as an administrative user on the client machine.
  2. Next, launch Component Services by clicking Start | Run | DCOMCNFG.
  3. In the left-hand window pane, expand Component Services | Computers | My Computer | DCOM Config.
  4. Locate and right-click on the OpcEnum entry in the list. Then, right-click and select Properties.
  5. Select the Security tab and locate Launch and Activation Permissions. Ensure that Customize is selected and then click Edit.
  6. Add the restricted user to the permissions list, allowing the user full access.
  7. Next, click OK. Then, click OK again to close the OpcEnum Properties window.
  8. Restart the OpcEnum service via the Services program (located in the Administrative Tools in the Control Panel).