使用搜索功能查看 Kepware 的信息库,其中包含 500 多篇知识库文章。缩小搜索结果范围,或在下面的搜索字段中输入您的查询。

或者,如果您无法找到解决方案,我们还有另一个资源:我们的 PTC eSupport Portal。 如果系统提示您登录 eSupport Portal,您可以使用“我的 Kepware”凭据。需要一个“我的 Kepware”帐户吗?在此处创建

搜索解决方案结果:
View All Solutions

Kepware Knowledge Base: Solution


How Does Device Scan Mode Work?


Last Update: 2018/11/12

Scan Mode allows users to specify both how the server scans the device for data and how to override the client application's update rate when necessary. It is especially helpful with more devices being developed for areas outside process automation. The parameters are:

  • Respect client specified scan rate: This mode uses the scan rate requested by the client.
  • Request data no faster than x: This mode specifies the maximum scan rate to be used.
  • Request all data at x: This mode forces tags to be scanned at the specified rate for subscribed clients.
  • Do not scan, demand poll only: This mode does not periodically poll tags that belong to the device or perform a read to get an item's initial value once it becomes active. It is the client's responsibility to poll for updates, either by writing to the _DemandPoll tag or by issuing explicit device reads for individual items.
  • Respect tag-specified scan rate: This mode forces static tags to be scanned at the rate specified in their static configuration. Dynamic tags are scanned at the client-specified scan rate.
Note: Synchronous and asynchronous device reads and writes are processed as soon as possible; they are not affected by the Scan Mode.