Devices Accessed through a USB-to-Serial Adapter Have Stopped Communicating


Last Update: 2018/11/7

Problem:
A project is configured to communicate with one or more devices through a USB-to-Serial adapter. Communications fail while running, but will resume after the device connections are reinitialized.

Possible Cause:
The USB Port's Power setting is configured to power the port down to save energy. To verify that this is the cause, check for the power light on the USB key. If it is off, the port is powered down.

Solution:
Change the USB Port's Power setting by opening the Device Manager and double-clicking on Universal Serial Bus Controllers. Adjust the settings as desired and then click OK.

Note:
This change may be required for several adapters.

Related Products
KEPServerEX